The challenge
Every HUD-assisted project needs an acceptable separation distance from above-ground tanks of flammable or explosive material nearby. Across seven projects that meant 153 tanks to find, photograph, measure, compute and document — and a tank measured in the field had to be the same tank on the map, in HUD’s calculator and in the report.
What we did
We put the whole survey in one shared record. Engineers capture tanks on the phone with photos and GPS; measurements typed as free text are read by a parser (with a language model for wordy notes) and the gallons are computed in code. Each tank’s distance to the Site and the Off-Site areas is computed, HUD’s official online calculator runs automatically, and its PDF is filed with the tank.
How technology helped
- 139 official HUD calculations filed without retyping.
- Excel, KMZ, maps, exhibit and report generated from the same records for five projects.
- A better rule. Measuring to the Off-Site corridor as well as the Site revealed a tank 180 ft from the corridor against a 238 ft separation distance. It had been marked compliant; the rule was changed and every project with tanks was recomputed.
Results
One record per tank, from the phone to the report — and a compliance error caught by a rule applied everywhere, not by luck.